The new power in energy! | Installation Cables and Flexible Cables

FROR 450/750 V

FROR 450/750 V

CEI 20-22 II

FROR 450/750 V
Application Areas

Used as power, network and lighting cable, exposed, in cable ducts or underground, for applications requiring flexibility.

Technical Specifications
Permissible Operating Temperature70 °C
Short Circuit Temperature160 °C
Test Voltage (AC)2 - 2.5 kV
Minimum Installation Temperature5 °C
Minimum Bending Radius12xD
Rated Voltage450/750 V
ConductorFlexible stranded copper
InsulationPVC
SheathPVC (Rz quality)
Technical Data
Rated Cross-sectionOverall Diameter of Cable (Approx)Current Carrying Capacity in AirConductor DC Resistance at 20°CNet Weight (Approx)Amount of Packing
mm²mmAohm/kmkg/kmm
2x0.756,20122655,501000
2x17,31619,576,451000
2x1.57,802413,391,331000
2x2.59,5337,98138,871000
2x410,50454,95181,291000
2x612,2583,3252,141000
3x17,721619,590,011000
3x1.58,2642413,3109,071000
3x2.510,07337,98167,071000
3x411,348454,95227,561000
3x613,17583,3317,861000
4x0.757,166122678,591000
4x18,411619,5107,901000
4x1.59,2182413,3136,401000
4x2.510,99337,98203,431000
4x412,401454,95279,551000
4x614,42583,3393,001000
5x19,3551619,5125,971000
5x1.510,232413,3160,151000
5x2.512,185337,98240,921000
5x413,94454,95340,051000
5x615,96583,3471,331000
7x19,951619,5162,931000
10x1131619,5266,33500
FROR 450/750 V is an installation cable compliant with CEI 20-22 II, featuring a flexible stranded copper conductor, PVC insulation and Rz quality PVC sheath. It is rated for 70 °C operating temperature, 160 °C short-circuit temperature, 2 - 2.5 kV AC test voltage, minimum 5 °C installation temperature and 12xD minimum bending radius.