Construction
1
Conductor: Aluminum Wire
2
Isolate: PVC Insulation
3
Filling: Polyethylene or PVC Filler
4
Armor: Galvanized Round Steel Wires
5
Outer Case: PVC Outer Sheath
Application Areas

Highly resistant to mechanical external influences thanks to galvanized steel tape armor. Also suitable for extreme transfers.

Standards
  •   TS IEC 60502-1
  •   IEC 60502-1
  •   VDE 0276
  •   IS 1516.1
Technical Specifications
Min. bending radius 12 x D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶