The new power in energy! | Installation Cables and Flexible Cables

U-1000 RVFV

U-1000 RVFV

XP C 32-321

U-1000 RVFV
Application Areas

The color-coded sheath enables 1.5-16 mm² sizing without measurement. UV resistance allows use in all weather conditions without additional protection.

Technical Specifications
Permissible Operating Temperature90 °C
Short Circuit Temperature250 °C
Test Voltage (AC)4 kV
Minimum Installation Temperature5 °C
Minimum Bending Radius15xD
Rated Voltage0.6/1 kV
ConductorSolid or stranded copper
InsulationXLPE
FillerPVC
ArmourDouble steel tape
SheathPVC
Technical Data
Rated Cross-sectionOverall Diameter of Cable (Approx)Current Carrying CapacityConductor DC Resistance at 20°CNet Weight (Approx)Amount of Packing
AirGround
mm²mmAAohm/kmkg/kmm
2 x 1018,64861041,831020,41000
2 x 1620,701151361,151267,41000
2 x 2524,201491730,7271688,01000
3 x 1019,4975871,831151,31000
3 x 1621,721001131,151455,91000
3 x 2525,501271440,7271967,51000
3 x 3527,901581740,5242404,11000
3 x 5031,231922060,3872976,51000
3 x 7036,842462540,2684384,81000
3 x 9541,613083060,1935611,1500
3 x 12045,083583470,1536692,6500
3 x 15049,784133930,1248047,2500
3 x 18554,984764440,09919778,0250
3 x 24061,175655180,075412248,3250
4 x 1021,0175871,831330,91000
4 x 1623,381001131,151706,61000
4 x 2527,831321440,7272340,81000
4 x 3531,071581740,5242888,71000
4 x 5035,071922060,3873604,71000
4 x 7041,392462540,2685310,7500
4 x 9547,072983010,1936918,1500
4 x 12050,953583470,1538296,1500
4 x 15056,364133930,12410011,0250
4 x 18563,164764440,099112212,9250
4 x 24070,375655180,075415373,4250
5 x 1022,3975871,831525,11000
5 x 1625,171001131,151976,91000
5 x 2530,141321440,7272749,81000
3 x 35+1628,451581740.524/1.1501899,91000
3 x 50+2524,601922060.387/0.7272495,21000
3 x 50+3525,121922060.387/0.5243369,51000
3 x 70+3536,472462540.268/0.5243534,31000
3 x 70+5037,392462540.268/0.3873527,91000
3 x 95+5041,543083050.193/0.3874507,9500
3 x 120+7045,663463580.153/0.2685635,7500
3 x 150+7049,583994120.124/0.2686647,5500
3 x 185+7053,904764440.0991/0.2687963,7250
3 x 185+9555,074764440.0991/0.1938307,9250
3 x 240+9560,225385010.754/0.19310250,4250
U-1000 RVFV is a 0.6/1 kV power cable compliant with XP C 32-321, featuring a solid or stranded copper conductor, XLPE insulation, PVC filler, double steel tape armour and PVC sheath. It is rated for 90 °C operating temperature, 250 °C short-circuit temperature, 4 kV AC test voltage, minimum 5 °C installation temperature and 15xD minimum bending radius.