The new power in energy! | Copper Low Voltage Cables

CBT / SVT

CBT / SVT

IEC 60502-1 | VDE 0276

CBT / SVT
Application Areas

Used with low mechanical stress, above plaster, in cable ducts, or underground as power and lighting cable.

Technical Specifications
Permissible Operating Temperature70 °C
Short Circuit Temperature160 °C
Test Voltage (AC)4 kV
Minimum Installation Temperature5 °C
Minimum Bending Radius12xD
Rated Voltage0.6/1 kV
ConductorSolid or stranded copper
InsulationPVC
SheathPVC
Technical Data
Rated Cross-sectionOverall Diameter of Cable (Approx)Current Carrying CapacityConductor DC Resistance at 20°CNet Weight (Approx)Amount of Packing
AirGround
mm²mmAAohm/kmkg/kmm
2 x 1.55,4919,52712,177,121000
2 x 2.56,6425367,41104,301000
2 x 47,5834474,61150,051000
3 x 1.58,7019,52712,1120,851000
3 x 2.510,0025367,41169,511000
3 x 411,0034474,61226,541000
3 x 612,1043593,082961000
3 x 1014,4059791,83448,361000
3 x 1616,5791021,15647,671000
3 x 2522,61001330,7259091000
3 x 3527,11251590,52312871000
4 x 1.59,419,52712,1144,581000
4 x 2.510,834474,61206,701000
4 x 41243593,08282,101000
5 x 1.510,8019,52712,1184,161000
5 x 2.511,8025367,41242,691000
5 x 413,0034474,61329,321000
5 x 614,4043593,08441,771000
5 x 1017,2059791,83669,321000
5 x 1619,90791021,15984,621000
5 x 2524,901061330,72715391000
5 x 3527,201291590,52420191000
5 x 5031,601571880,3872704,1500
CBT is a 0.6/1 kV power cable compliant with IEC 60502-1 and VDE 0276, featuring a solid or stranded copper conductor, PVC insulation and PVC sheath. It is rated for 70 °C operating temperature, 160 °C short-circuit temperature, 4 kV AC test voltage, minimum 5 °C installation temperature and 12xD minimum bending radius.