CBT / SVT
IEC 60502-1 | VDE 0276
Application Areas
Used with low mechanical stress, above plaster, in cable ducts, or underground as power and lighting cable.
Technical Specifications
| Permissible Operating Temperature | 70 °C |
| Short Circuit Temperature | 160 °C |
| Test Voltage (AC) | 4 kV |
| Minimum Installation Temperature | 5 °C |
| Minimum Bending Radius | 12xD |
| Rated Voltage | 0.6/1 kV |
| Conductor | Solid or stranded copper |
| Insulation | PVC |
| Sheath | PVC |
Technical Data
| Rated Cross-section | Overall Diameter of Cable (Approx) | Current Carrying Capacity | Conductor DC Resistance at 20°C | Net Weight (Approx) | Amount of Packing |
| Air | Ground |
| mm² | mm | A | A | ohm/km | kg/km | m |
| 2 x 1.5 | 5,49 | 19,5 | 27 | 12,1 | 77,12 | 1000 |
| 2 x 2.5 | 6,64 | 25 | 36 | 7,41 | 104,30 | 1000 |
| 2 x 4 | 7,58 | 34 | 47 | 4,61 | 150,05 | 1000 |
| 3 x 1.5 | 8,70 | 19,5 | 27 | 12,1 | 120,85 | 1000 |
| 3 x 2.5 | 10,00 | 25 | 36 | 7,41 | 169,51 | 1000 |
| 3 x 4 | 11,00 | 34 | 47 | 4,61 | 226,54 | 1000 |
| 3 x 6 | 12,10 | 43 | 59 | 3,08 | 296 | 1000 |
| 3 x 10 | 14,40 | 59 | 79 | 1,83 | 448,36 | 1000 |
| 3 x 16 | 16,5 | 79 | 102 | 1,15 | 647,67 | 1000 |
| 3 x 25 | 22,6 | 100 | 133 | 0,725 | 909 | 1000 |
| 3 x 35 | 27,1 | 125 | 159 | 0,523 | 1287 | 1000 |
| 4 x 1.5 | 9,4 | 19,5 | 27 | 12,1 | 144,58 | 1000 |
| 4 x 2.5 | 10,8 | 34 | 47 | 4,61 | 206,70 | 1000 |
| 4 x 4 | 12 | 43 | 59 | 3,08 | 282,10 | 1000 |
| 5 x 1.5 | 10,80 | 19,5 | 27 | 12,1 | 184,16 | 1000 |
| 5 x 2.5 | 11,80 | 25 | 36 | 7,41 | 242,69 | 1000 |
| 5 x 4 | 13,00 | 34 | 47 | 4,61 | 329,32 | 1000 |
| 5 x 6 | 14,40 | 43 | 59 | 3,08 | 441,77 | 1000 |
| 5 x 10 | 17,20 | 59 | 79 | 1,83 | 669,32 | 1000 |
| 5 x 16 | 19,90 | 79 | 102 | 1,15 | 984,62 | 1000 |
| 5 x 25 | 24,90 | 106 | 133 | 0,727 | 1539 | 1000 |
| 5 x 35 | 27,20 | 129 | 159 | 0,524 | 2019 | 1000 |
| 5 x 50 | 31,60 | 157 | 188 | 0,387 | 2704,1 | 500 |
CBT is a 0.6/1 kV power cable compliant with IEC 60502-1 and VDE 0276, featuring a solid or stranded copper conductor, PVC insulation and PVC sheath. It is rated for 70 °C operating temperature, 160 °C short-circuit temperature, 4 kV AC test voltage, minimum 5 °C installation temperature and 12xD minimum bending radius.